Input of 10/16/20KVA Online UPS - Emerson Make Liebert: Rated voltage 3-phase: 380Vac Voltage range 304Vac ~ 478Vac, at full load 228Vac ~ 304Vac, linear derating 228Vac, at half load Rated frequency 50Hz/60Hz Frequency range 40Hz ~ 70Hz Power factor â¥0.99, at full load; â¥0.98, at half load
Output : Rated power 9kw,14.4kW&18kW Voltage 220Vac ± 1% (3-phase balance load) Frequency sync range Rated frequency ± 2Hz (range is settable: ±0.5Hz ~ ±3Hz) Frequency track rate 1Hz/s. Range is settable: 0.1Hz/s ~ 3Hz/s (single), 0.2Hz/s (parallel) Rated power factor 0.9 Crest factor 3:1 Voltage harmonic : distortion <2% (linear load), <5% (non-linear load) Dynamic response : recovery time 60ms Overload capacity 105% ~ 125%, 5min 125% ~ 150%, 1min Bypass voltage Upper limit: +10%, +15% or +20%; default: +15% Lower limit: -10%, -20%, -30% or -40%; default: -20% Mains efficiency >93%, up to 94% Battery Type Sealed, lead-acid, maintenance-free battery Cell No. 30, 32, 34, 36, 38, 40 Rated voltage 360Vdc ~ 480Vdc Charge power 4.5kW Transfer time MainsââBattery 0ms InverterââBypass Synchronous transfer: â¤1ms Asynchronous transfer (default): â¤20ms Or 40ms, 60ms, 80ms and 100ms are available Noise â¤58dB Panel display mode LED and LCD Safety IEC/EN62040-1-1 EMC Conduction emission IEC/EN62040-2 Immunity Iâ¤16Aï¼IEC/EN61000-3-3, 16A<Iâ¤75A, IEC/EN61000-3-11 Harmonic current Iâ¤16Aï¼IEC/EN61000-3-2, 16A<Iâ¤75A, IEC/EN61000-3-12, YD/T1095-2001, level 2ï¼15%
|